Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-UTL-0223-00044
Parcel: 129150020

Address:
1702 S EUCLID AV

Review Status: Requires Resubmit

Review Details: UTILITIES REVIEW v.5

Permit Number - TC-UTL-0223-00044
Review Name: UTILITIES REVIEW v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2024 Site Engineering NOT REQUIRED
05/09/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/09/2024 Commercial Electrical REQUIRES RESUBMIT The information requested per the previous electrical plan review; Please address the electrical plan review comments and provide a written response. 1 Ref; Electrical line diagram, Plan E3. Indicate fuse sizes and types or more detail for the OCPD utilized as the electrical main service disconnect. Ref; 2018 IBC section 107.2.1, 2017 NEC
The information requested must be included on the plans (Line Diagram).
04/11/2024 PDSD Application Completeness Express REVIEW COMPLETED