Permit Number: TC-UTL-0125-00001
Parcel: 12004003J

Review Status: In Review

Review Details: PRIVATE UTILITY v.1

Permit Number - TC-UTL-0125-00001
Review Name: PRIVATE UTILITY v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2025 Site Engineering NOT REQUIRED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Site Engineering Complex PENDING ASSIGNMENT
02/03/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical TC-UTL-0125-00001 (1110 W IRVINGTON RD TUCSON, AZ 85714)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
2. Provide complete Site-utility plans for electrical.
02/10/2025 Commercial Plumbing REQUIRES RESUBMIT Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
02/03/2025 Outdoor Lighting REQUIRES RESUBMIT Outdoor Lighting Review • TC-UTL-0125-00001 (1110 W IRVINGTON RD TUCSON, AZ 85714)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:

1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan
2. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
3. Show compliance to total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2.
4. Submit catalogue or specification sheets of the proposed light fixture illustrating the type of fixture they are whether full cut-off or unshielded.

5. Provide calcs for total lumens allowed and total lumens proposed per acre for Full Cut Off and Unshielded per table 401.1.Must include existing to remain lighting.

6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

7. Specify any exceptions used.

8. Provide Curfew lighting controls If applicable Per section 403.

9. Provide complete compliance with the 2018 IECC for the interior and exterior lighting where applicable. Do not confuse the Outdoor Lighting Code with the IECC.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/29/2025 PDSD Application Completeness Express REVIEW COMPLETED