Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2024 Commercial Electrical APPROVED
01/08/2024 Fire New Construction NOT REQUIRED
02/01/2024 Site Engineering NOT REQUIRED
02/02/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/02/2024 Commercial Building REQUIRES RESUBMIT Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review..
1. Submit structural calculation proving that the existing roof is able to receive all of the proposed roof equipment.
2. Submit structural calculation and detail drawing as to the mounting of equipment onto the side of the existing structure. The type of bolt, it size, embedment depth, adhesive being use, the number of bolts used, etc.
3. Please resubmit.
01/29/2024 Entitlements REQUIRES RESUBMIT This installation requires the PDSD Director Approval Procedure per the following:

a. Wireless communication , provided:
(1) The antennas are mounted on the wall or roof of a building, or concealed within an architectural or structural element of the building, not exceeding the permitted height of the building;

You may request PDSD Director's Review through the "Request" tab in your permit, accessible through Manage My Work in TDC Online.
01/30/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-UTL-0124-00001
5255 E WILLIAMS CI. – PAD-1 (1st Review)
Collocation of antennas

TRANSMITTAL: January 30, 2024
This site is located in PAD-1 (UDC 4.7.24).

1. Unit this plan is approved by the Entitlements Section Zoning cannot approve the plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
01/09/2024 IT Infrastructure Engineering REVIEW COMPLETED
01/04/2024 PDSD Application Completeness REVIEW COMPLETED