Permit Number: TC-RES-1225-06180
Parcel: 113094560

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.3

Permit Number - TC-RES-1225-06180
Review Name: RESIDENTIAL ADD/ALT v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/23/2026 Residential Building - Standard REQUIRES RESUBMIT TC-RES-1225-06180 2nd
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes.

Provide a response letter on separate file when submitting the updated construction plan set.

SITE PLAN:

1. The roof structure may not extend to a point closer than 3 feet from the neighboring property line without fire rated protection for fire spread. Provide compliance with R302.1 (City of Tucson Amended) by removing the roof placed within 3 feet of the property line or, provide a complete wall barrier (height of structure and with lateral support) with not less than one-hour fire-resistive construction in compliance with IBC Table 721.1(2).

PLANS:

1. Field welding requires a completed special inspection request form for review with the permit plans, R109.2. Obtain an inspector and provide a certified inspector seal on the form found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Inspections and provide with next submittal.

If you have any questions, please contact: