Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL ADD/ALT v.1
Permit Number - TC-RES-1225-05890
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/17/2025 | Residential Engineering | NOT REQUIRED | |||
| 12/23/2025 | Residential Zoning | NOT REQUIRED | |||
| 01/07/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/07/2026 | Residential Building - Standard | REQUIRES RESUBMIT | Please resubmit once the comments below have been addressed 1. Please Provide electrical load calculations for determining the service panel size, E3602.2. 2. Provide a panel schedule: panel size, circuit numbers, ampacity, and wire sizes, E3404.11, E3706.2. 3. All smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are not removed, existing bedrooms may be equipped with battery operated smoke detectors, R314. 4. Provide manual J calculations for new HVAC system. |
||
| 12/16/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |