Permit Number: TC-RES-1225-05890
Parcel: 106062790

Address:
1055 W KING ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-1225-05890
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/17/2025 Residential Engineering NOT REQUIRED
12/23/2025 Residential Zoning NOT REQUIRED
01/07/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/07/2026 Residential Building - Standard REQUIRES RESUBMIT Please resubmit once the comments below have been addressed
1. Please Provide electrical load calculations for determining the service panel size, E3602.2.
2. Provide a panel schedule: panel size, circuit numbers, ampacity, and wire sizes, E3404.11, E3706.2.
3. All smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are not removed, existing bedrooms may be equipped with battery operated smoke detectors, R314.
4. Provide manual J calculations for new HVAC system.
12/16/2025 PDSD Application Completeness Express REVIEW COMPLETED