Permit Number: TC-RES-1224-07519
Parcel: 128072090

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-1224-07519
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2025 Site Zoning APPROVED
03/18/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/17/2025 Residential Building REQUIRES RESUBMIT TC-RES-1224-07519 2nd

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments and building ordinances for all dwellings.

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

PLANS:

1. Provide a complete roof framing plan with a ridge member sized with appropriate load carrying capacity. Show the ridge structural member as a full-sized beam with appropriate load bearing rating when the roof pitch is less than 3” to 12”, R802.3. Consider a glu-lam beam or show a mid-span support post with foundation.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms including the bedroom, R303.9. Add a mini-split unit within the bedroom.

ELECTRICAL PLANS:

1. Show an appropriate sub-panel feeder and breaker size for the calculated demand, E3705.5. The #6 feeder and 60 AMP breaker are undersized.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
03/03/2025 PDSD Application Completeness Express REVIEW COMPLETED