Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1224-07365
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/18/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1224-07365 (7331 E 32ND ST TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Aerial views of the property show the MSP at the back porch, not the location shown on the plans. Clarify if the MSP is being relocated as part of the upgrade. Show the location of the Overhead Electrical Line on the site plan. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 12/18/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |