Permit Number: TC-RES-1224-07328
Parcel: 131072270

Address:
6211 E 29TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-1224-07328
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/24/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/24/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT FROM: PDSD Residential Review Section

PROJECT: TC-RES-1224-07328
PANEL UPGRADE
6211 E 29TH ST

TRANSMITTAL DATE: December 24TH, 2024

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).
 
1. Show the location of the meter/panel to be upgraded. The location marked on the site plan is inside the building.
2.TEP usually requires the service panel on the property at the closest building to the service transformer. You may need to work with TEP to provide a safe and code compliant location for the service equipment.

If you have any questions please email building_official@tucsonaz.gov