Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-1224-07328
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/24/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/24/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | FROM: PDSD Residential Review Section PROJECT: TC-RES-1224-07328 PANEL UPGRADE 6211 E 29TH ST TRANSMITTAL DATE: December 24TH, 2024 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Show the location of the meter/panel to be upgraded. The location marked on the site plan is inside the building. 2.TEP usually requires the service panel on the property at the closest building to the service transformer. You may need to work with TEP to provide a safe and code compliant location for the service equipment. If you have any questions please email building_official@tucsonaz.gov |
||
| 12/23/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |