Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1224-07293
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2024 | Site Engineering | NOT REQUIRED | |||
| 12/18/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/16/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1224-07293 (6129 E 2ND ST TUCSON, AZ 85711) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans and a written response letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response letter addressing the comments below maybe be delayed until the response letter is received. For additional questions: Building_Official@tucsonaz.gov 1. Note and specify all piping material and sizes, P2609. 2. Non-metallic water line requires blue tracer line. 3. Minimum burial depth, 12'', P2603.5. 4. PRV required if PSI greater than 80 5. A minimum 1'' service pip is required when supplying more than 9.5 fixtures |
||
| 12/16/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |