Permit Number: TC-RES-1224-07291
Parcel: 125070770

Address:
721 N FORGEUS AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-1224-07291
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2025 Site Zoning APPROVED
01/31/2025 Site Engineering NOT REQUIRED
01/07/2025 Site Landscape NOT REQUIRED
01/31/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/09/2025 Residential Building REQUIRES RESUBMIT TC-RES-1224-07291
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

Clarify if the structure is a sleeping quarters (without kitchen) or an Accessory Dwelling Unit (ADU) which requires a kitchen for code compliance. Update the description on the plans to Sleeping Quarters or add cooking facilities needed for an ADU.

Each dwelling unit with kitchen requires a separate Pima County assigned street address after Zoning approval, R319. Show Pima County assigned unit numbers at each dwelling on the site plan. https://www.pima.gov/1010/Addressing-Frequently-Asked-Questions

An impact fee payment is required for an ADU at the time of permit payment. Not required for Sleeping Quarters.

Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007 if an ADU. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electrical, and sewer, R106.1.1. Show the location and size of lines with connection points, R106.1.1. Identify the utility lines requiring upgrade or replacement.

PLANS:

1. Notate a cool (white) roof finish (greater than 60 SRI) as required by the ADU provisions. Not required for Sleeping Quarters.
2. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. Include all threshold conditions for a route from the exterior into the ADU. Not required for Sleeping Quarters.

SECTIONS - DETAILS:

1. Show footings at least 12” below the undisturbed ground surface, R403.1.4. Update the 8” post footer depth to 12” at section 1.0 on sheet S3.0.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF. Clarify the ceiling/roof insulation detail showing the air-impermeable rigid insulation material adhered to either side of the roof sheathing and the batt insulation in contact with the roof material.

PLUMBING PLANS:

1. The Tucson Water Department limits flow rates for the water meter size in compliance with P2903.7. Show an appropriate water meter size for the additional demand.
2. Show water supply shut off and positioned for controlling all supply to the building, P2903.9.1. Change the shower branch line connection point.
3. Show the water heater BTU rating, P2801.1.
4. Show each gas pipe segment sized in conformance with Table G2413.4(1). The ¾” gas pipe may require upgrading with developed length and demand consideration.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust for an ADU, R303.4; N1103.6 & M1505.4. Identify the device model number providing an adjustable setting and note the minimum continuous setting. A one-bedroom dwelling under 1501 SF requires a 30 CFM continuous setting. Not required for Sleeping Quarters.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to ADU plans.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
01/02/2025 PDSD Application Completeness Express REVIEW COMPLETED