Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-RES-1224-07219
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/02/2025 | Other Inspection Reports (Deferred Submittal) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-RES-1224-07219 ADDRESS/PARCEL: (1019 N ANITA AV TUCSON, AZ 85705) Submit your revised reports along with a detailed response letter which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. COMMENTS: 1. A/C unit sizing does not align with the drawings or the Manual J. Manual J specifies both units should be below 2 tons. 1.7 and 1.5 tons for the 3 bedroom and 2 bedroom respectively. Design drawings also show different sized units for each dwelling. Since this is new construction the construction quality should be listed in the Manual J as “Tight”. The proposed unit for both dwellings is 2.5 tons and would be oversized based on the information provided. Please correct the Manual J inputs to ensure correct A/C sizing. 2. Please resubmit. Should you have any questions about these comments, I can be reached at ian.gillaspie@tucsonaz.gov. |
||