Permit Number: TC-RES-1224-07175
Parcel: 117041600

Address:
628 N 10TH AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1224-07175
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/11/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT 1. Provide total demand from all appliances, G2413.2.

2. Provide a gas piping plan showing the connection from the meter to ALL attached appliances. Include pipe size, type, and length. Show connection, lengths, and sizes, from gas meter to all gas appliances. Modifications to the gas system requires the submission of a gas pipeline template (or equivalent), G2401.1, G2413.1, R301.1.
Gas Lines- Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes.
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_handout_2018_irc_2019.2.4.pdf

3. Provide what work was done during the repair
building_official@tucsonaz.gov
12/11/2024 PDSD Application Completeness Express REVIEW COMPLETED