| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2025 | Site Engineering | NOT REQUIRED | |||
| 01/07/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/19/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1224-06996 (2550 S KEVIN DR TUCSON, AZ 85748) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Provide consistent information and OCPD/Conductor sizes. See conductor tag 4 on sheets E1.1 – E1.3, it is shown as both a #3 and a #4 conductor. 2. The existing OCPD shown in the “New Solar Load Center” is shown as 40A, but the calculations on Sheet E1.3 show this as a 20A OCPD. 3. The “PV+ESS Breaker” in the Tesla Backup Gateway is shown as 100A, but the calculations on sheet E1.3 show this as an 80A OCPD. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||