Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-1223-10331
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/24/2024 | Site Engineering | NOT REQUIRED | |||
01/24/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/09/2024 | Residential Building | REQUIRES RESUBMIT | TC-RES-1223-10331 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections. Consider using a design professional if unfamiliar with construction documentation. Separate the submitted files with construction plans and support documents in different files. Place sheet numbers on each sheet of construction plans. Provide a clear and concise construction plan set. Sample Porch (Carport) plans are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits SITE PLAN: Provide a site plan showing dimensions of buildings and utilities, R106.1.1. Show the location of all utility lines from property line to building(s) along with required alterations. STRUCTURAL PLANS: 1. Provide complete structural (roof framing) plans showing compliance with the IRC or provide an Arizona structural engineer plan set showing performance compliance, R301.1. 2. The proposed Patio Cover may be sited within the 3’ fire separation distance from a property line. Show compliance with R302.1 (City of Tucson Amended) by providing a wall with one-hour rated materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3, R106.1 or remove any structure closer than 3 feet to the property line. SECTIONS - DETAILS: 1. Provide a structure section showing existing and proposed features including a foundation, sills, anchoring, framing, fasteners, and sheathing, R106.1. 2. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show with dimensions the exterior wood siding, insulation, interior sheathing, and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5. If you have any questions, please contact: PDSD-Residential@tucsonaz.gov City of Tucson Residential Plan Review Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services |
||
01/04/2024 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-RES-1223-10331 - CE-VIO1123-06470 636 N CAMINO SANTIAGO – R-1 Detached Carport (1st Review) TRANSMITTAL DATE: January 4, 2024 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the R-1 zone (UDC 4.7.7). A single family residence is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 1. The site plan shall meet the requirements for a residential plot plan found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example, to include but not limited to: a. The site plan shall be drawn at an engineering scale, i.e. 1” 10’, 1” = 20’. b. Provide a lot coverage calculation that meets the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements. 2. Per UDC Table 6.3-2.A the minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line. Perimeter yard setbacks are based on a wall height measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. Where the wall meets the eave of the roof. Per UDC Article 6.4.5.B.2 the setback is measured from the post supporting the structure for carport type structures. Clearly show the post and provide setback dimensions from the post to the east and south property line. As no setback dimension was provided from the structure to the south property line and no height dimension was provided from design grade to the highest point of the wall on the south end Zoning cannot determine setback requirements to the south property line. What appears to be a 2’ setback to the east property does not meet the minimum 6’-0” perimeter yard setback and at a minimum will require a neighbors setback waiver, UDC Article UDC Article 6.6.2.D. To secure this neighbor setback waiver the following statement must be provided on the plot plan and be signed and dated by the adjacent property owner(s): My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan. Signature: _____________________________ Date: _________________________________ As the east perimeter yard setback does not meet requirements and it appears that the south does not meet the required setback waivers are required from the owners of the properties at 646 N. Camino Santiago and 641 N. Avenida Calma. If you are not able to secure the required waivers a Design Development Option (DDO) must be submitted and approved to reduce the required setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
01/02/2024 | PDSD Application Completeness | REVIEW COMPLETED |