Permit Number: TC-RES-1223-10247
Parcel: 110050290

Address:
2924 N VENICE AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1223-10247
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2024 Site Engineering NOT REQUIRED
12/28/2023 Site Zoning NOT REQUIRED No change in floor plan that triggers Zoning review.
01/24/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/08/2024 Residential Building REQUIRES RESUBMIT TC-RES-1223-10247
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation, R806. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing and tightly applied (minimum) R-30 insulation, R806.5. A single layer of batt insulation does not provide the required condensation control. Air space between roof sheathing and ceiling insulation requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2.

MECHANICAL PLANS:

1. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1.

ELECTRICAL PLANS:

1. Show the location of a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
2. Panelboards and overcurrent protection devices shall not be in clothes closets or bathrooms, E3405.5. Show the relocated subpanel on sheet E1.0.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
12/26/2023 PDSD Application Completeness REVIEW COMPLETED