Permit Number: TC-RES-1223-10224
Parcel: 121063390

Address:
5533 E MABEL ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1223-10224
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/22/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1223-10224 (5533 E MABEL ST TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Note and specify all piping materials (BIP or PEX), G2412.9.
2. Provide the max demand of each attached appliance, G2413.4.
3. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) Polyethylene Plastic Pipe.
4. Provide the length as measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
5. Provide a Yellow tracer wire for non-metallic pipe, G2415.17.3.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/21/2023 PDSD Application Completeness Express REVIEW COMPLETED