Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-RES-1223-10171
Parcel: 141386530

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1223-10171
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2024 Site Engineering NOT REQUIRED
01/11/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/05/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT TC-RES-1223-10171 Resubmit comment

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Wind speed on the structural documents and construction plans are incorrect. For wind uplift use 115 mph in 3sec gust, Table R301.2(1). https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf

For any questions contact: building_official@tucsonaz.gov
12/19/2023 PDSD Application Completeness REVIEW COMPLETED