Permit Number: TC-RES-1223-10094
Parcel: 114465330

Address:
7782 E CLEARY WY

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1223-10094
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/29/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/29/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1223-10094 (7782 E CLEARY WY TUCSON, AZ 85715)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

Structural Review:
1. For wind uplift use 115 mph in 3sec gust, IRC Table R301.2(1). Show this wind value on the plans: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf

>> Provide the following structural calculations.
2. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, or provide an engineer’s calculation, and sealed design, IRC R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems

Electrical Review:
3. Note on the plans: PV breaker must be at the opposite end of the bus bar from the main service breaker, 2017 NEC 705.12(B)(2)(3)(b).

4. Provide electrical load calculations for determining the main service panel/breaker size, E3602.2. Derating of the main breaker requires load calculations.

5. TEP will not allow multiple Utility DG Meters. Either provide TEP approval of the multiple Utility DG Meters, or combine the PV sources through on Utility DG Meter.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/14/2023 PDSD Application Completeness Express REVIEW COMPLETED