Permit Number: TC-RES-1223-10067
Parcel: 136240580

Address:
6722 E 38TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1223-10067
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2024 Site Engineering NOT REQUIRED
01/10/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/26/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1223-10067 (6722 E 38TH ST TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. After a review of aerial views (https://maps2.tucsonaz.gov/Html5Viewer/?viewer=maptucson#) of the property, it appears that PV modules are mounted on an unpermitted structure on the south-west side of the building. Searching city records through PRO (https://pro.tucsonaz.gov/address_search/) found no permit history for this structure. Either provide completed permit and inspection documentation, apply for and complete permit review and inspections for the structure or remove the PV modules from the unpermitted structure.
Structural review:
1. For wind uplift use 115 mph in 3sec gust, IRC Table R301.2(1). Show this wind value on the plans: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf

>> Provide the following structural calculations.
2. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, or provide an engineer’s calculation, and sealed design, IRC R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov