Permit Number: TC-RES-1223-10065
Parcel: 118271250

Address:
2301 W OCELOT DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1223-10065
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/07/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1223-10065 (2301 W OCELOT DR TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. The conductors in raceway #7-9 are undersized for the given current, 142.06A (See backfeed Breaker Sizing table on sheet PV-4A for total current), Reference NEC 690.8(A)(3) and (B)(1). Show these conductors sized for the given total current. Reference NEC 310.15, Table 310.15(B)(2)(a), 310.15(B)(2)(b) and 310.15(B)(3)(a). The adjusted conductor rating may not be less than the calculated Conductor Sizing.
2. The minimum size required for this conductor, (Between the 200A dedicated load center and the 400A sub panel), is 1/0 CU. NEC 690.8(B).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov