Permit Number: TC-RES-1223-10031
Parcel: 11308060A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1223-10031
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/12/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1223-10031 (1024 E ADELAIDE DR TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Notate and specify all piping materials and sizes, P2608.
2. Show the main line sewer line sized per R3004. Provide all fixture drainage units that will use this main line. Pima County records show 3 units on this address.
3. Separate submittal to Pima County RWRD is required for new connections to sewer. Contact sewer@pima.gov for review and assessment.
4. Provide Pima County RWRD permit number and permit approval for the new sewer connection.

5. Provide elevation measurements for Next Upstream Manhole and Finished Floor Elevation. Provide Backwater valve protection as/if required.
Backwater valve protection:
https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf Section P3008.1 Where required. Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole cover in the sewer, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/12/2023 PDSD Application Completeness Express REVIEW COMPLETED