Permit Number: TC-RES-1223-09961
Parcel: 128061300

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1223-09961
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2024 Site Engineering NOT REQUIRED
01/02/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/19/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT TC-RES-1223-09961 Resubmit comment

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. No windspeed is listed. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability for 115 MPH, or provide an engineer’s calculation, and sealed design, R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems

2. On sheets PV6 and PV6.1 show AWG wire size for tag C0.

3. On sheet PV6 Show a Tap conductor length of 10' or less per NEC 240.21(B)(1)

For any questions contact: building_official@tucsonaz.gov
12/07/2023 PDSD Application Completeness Express REVIEW COMPLETED