Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-1223-09912
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/25/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | TC-RES-1223-09912 Resubmit comment Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Residential systems, including ESS, with total production of 100A or greater, require a design and calculations provided by an Arizona registered Electrical Engineer, R106.1. 2. Provide a fused disconnect per NEC 240.21(5)(3) and TEP SR 702. 3. The #2 AWG conductor is undersized for the given load. Conductors shall be protected with OCPD’s having a rating not exceeding the allowable ampacity of the conductor, IRC E3705.5, reference NEC 310.15, 240.4. For any questions contact: building_official@tucsonaz.gov |
||
| 01/05/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |