Permit Number: TC-RES-1223-09851
Parcel: 138233430

Address:
831 W ACADIA DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1223-09851
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/05/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1223-09851 (831 W ACADIA DR TUCSON, AZ 85756)
Revision 1: Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. The EOR’s seal must be placed back on the updated plans for the structural sheets, R106.1. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
2. The #10 awg CU conductor, for tag 6, 7 and 8, is undersized for the given 40A OCPD in the fused disconnect. OCPD for copper conductor may not exceed 30A for #10 rating required by NEC 240.4(D)(small conductors). Show conductors sized per the previously approved plans.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov