Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-1222-01701
Parcel: 128121180

Address:
4765 E 17TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-RES-1222-01701
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/25/2023 Residential Building REQUIRES RESUBMIT Provide a Mechanical Upgrade Template for a new installation. See https://www.tucsonaz.gov/pdsd/residential-permits for the document.

Clarify if gas piping was existing without change or replaced or newly installed for the new HVAC system. A system of 73' developed length with a 135,000 Btu demand requires a 1" main line and a 3/4" branch line to the furnace.
12/27/2022 PDSD Application Completeness Express REVIEW COMPLETED