Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-1222-01674
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/10/2023 | Site Engineering | NOT REQUIRED | |||
| 12/28/2022 | Site Landscape | NOT REQUIRED | |||
| 01/25/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/25/2023 | Residential Building | REQUIRES RESUBMIT | 1. Provide plans with wind load calculations sealed by an Arizona engineer for the pre-designed assembly, R106.1. 2. TEP usually requires the service panel on the property at the closest building to the service transformer. The overhead service conductor over the proposed building requires an 8’ clearance above the roof, E3604.2.1. The necessary mast height at the existing panel location is not a feasible installation. 3. TEP may require the service panel for the property at the closest building to the service transformer. A service line change or a new meter location must be coordinated with TEP for approval. Show an underground feeder from a metered service panel to the more distant dwelling. |
||
| 01/11/2023 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: TC-RES-1222-01674 6449 E Calle Dened - R-1 Detached Garage (1st Review) TRANSMITTAL: January 11, 2023 Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal. This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. 1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. Additional comments maybe forth coming. 2. Provide fully dimensioned elevations drawings. The drawings shall clearly show wall height dimensions from design grade to the highest point of all walls. and from design grade to the midpoint of the pitched roof. These dimensions are needed to verify perimeter yard setbacks and proposed building height. Per UDC Table 6.3-2A the minimum setback to the rear property line is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing rear property line. The minimum side street perimeter yard setback is 10’-0”, UDC Article 6.4.5.C.1.b. Per UDC Article 6.6.3.D Accessory structures, except for accessory dwelling units, shall not exceed 12 feet in height, unless attached, as stated below, to a principal structure. 3. Per UDC Article 6.6.3.E The total gross floor area (gfa) of all accessory structures shall not exceed 50% of the gfa of the principal structure. Clearly demonstrate that the proposed detached garage does not exceed the 59% gfa of the main dwelling. If the detached garage exceeds the 50% one of two things shall be done, 1) attach the garage to the main dwelling with a minimum 5’-0” wide roofed structure that can support a 20 lb live load or apply for a variance. Board of Adjustment application/requirements can be found at: https://www.tucsonaz.gov/files/pdsd/codes/Zoning_Administration_Application_BA_fillable.pdf. The Board of Adjustment is a separate submittal from this building plan and is submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. Contact of the Board of Adjustment is Mark Castro at Mark.Castro@tucsonaz.gov. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov |
||
| 12/27/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |