Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-1222-01545
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/27/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/27/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1222-01545 (334 W CALLE ANTONIA TUCSON, AZ 85706) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Provide updated PV Backfeed Breaker Sizing calculations. See sheet PV-4. My calculations for the IQ8Plus micro inverters give a much higher value, 28 * 1.21A * 1.25 = 42.35A. Reference NEC 690.8(A)(3) and (B)(1). Show a complete calculation for determining OCPD. 2. With updated OCPD calculations, Provide Main Service Panel (MSP) taps in compliance with NEC 705.12 705.12(B)(2)(3) b Busbars. 120% bus bar rule. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||