Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1222-01539
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2023 Light Residential Building Review (OIP) APPROVED
01/12/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/30/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1222-01539

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
Roof framing size and spacing is indicated inconsistently. Structural calculations reference 11-7/8” TJI 210 @ 24” oc. Sheet PV-3 Table 1 indicates “TJI Rafter” at 12” oc. Sheet PV-3 Solar Array Section note indicates dimensions but not weight and spacing of rafters. Confirm size and spacing of existing roof rafters and provide the correct designation throughout all drawings, calculations, and certifications


BUILDING REVIEW COMMENTS:
CONDITIONALLY APPROVED
Requested variance for BOS ACD/PM MORE THAN 10 FT AWAY FROM METER (Sheet PV-2) may be granted only by the jurisdiction. Approval of the request is neither confirmed nor implied.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
CONDITIONALLY APPROVED
Requested variance for BOS ACD/PM MORE THAN 10 FT AWAY FROM METER (Sheet PV-2) may be granted only by the jurisdiction. Approval of the request is neither confirmed nor implied.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/16/2022 PDSD Application Completeness Express REVIEW COMPLETED