Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.3
Permit Number - TC-RES-1222-01527
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/08/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/08/2023 | Residential Building | REQUIRES RESUBMIT | TC-RES-1222-01527 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: Separate the submitted pages with construction plans and support documents in different files. PLANS: 1. Show compliance with R310 providing egress from bedrooms with minimum net clear opening area of 5.7 SQ FT (5 SQ FT 1st floor). Also, show the minimum net clear opening dimension of 24” height and 20” width, and maximum sill height of 44”. Update one of the window details for Sleeping Quarters bedroom. ELECTRICAL PLANS: 1. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, E3404.12. 2. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2Provide proposed wiring details showing code compliant device locations and circuit sizes. 3. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6. 4. Show one 20 AMP branch circuit in the laundry area; this circuit may not serve other locations, E3703.3 and 3901.8. 5. Show the receptacle outlet located within 6’ of a sink with ground fault circuit interrupting protection, E3902. Please contact the plans reviewer if you have any questions: Ken Van Karsen (520) 837-4912 PDSD-Residential@tucsonaz.gov City of Tucson Residential Plan Review Submit a corrected plan set at https://www.tucsonaz.gov/pdsd |
||
| 07/24/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |