Permit Number: TC-RES-1222-01357
Parcel: 134171090

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1222-01357
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2022 Site Zoning APPROVED
12/21/2022 Site Engineering NOT REQUIRED
01/30/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/30/2023 Residential Building REQUIRES RESUBMIT TC-RES-1222-01357
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS :

1. This review is for an addition of dwelling space at 7232 E Montecito Dr. A separate permit request is required for a new or updated C of O for a Care Home. Such a request requires a building sprinkler system, 2018 IBC 310.4.1.

SECTIONS - DETAILS:

1. Show a cross-section detail for the new exterior wall, R106.1.1. Show the minimum 12” footing depth below the undisturbed ground surface with 12” minimum width for wood framed walls, R403.1. Show ½” exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5) with minimum ½” diameter anchor bolt and treated sill plates, R602.10.8 & R403.1.6. This may require a concrete stem when the floor is less than 6” above grade. Update detail #4 on S1.0.
2. Attic space requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
12/08/2022 PDSD Application Completeness Express REVIEW COMPLETED