Permit Number: TC-RES-1222-01349
Parcel: 119041120

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1222-01349
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2023 Light Residential Building Review (OIP) APPROVED
01/09/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/09/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1222-01349

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
Revise per building comments


BUILDING REVIEW COMMENTS:
DENIED
1. Not fewer than two pathways, on separate roof planes from lowest roof edge to ridge and not less than 36 inches wide, shall be provided on all buildings. Not fewer than one pathway shall be provided on the street or driveway side of the roof. (IRC R324.6) Revise Roof #2/Roof #3 layout to provide the required pathways.
2. For photovoltaic arrays occupying not more than 33 percent of the plan view total roof area, not less than an 18 inch clear setback is required on both sides of a horizontal ridge. For photovoltaic arrays occupying more than 33 percent of the plan view total roof area, not less than a 36 inch clear setback is required on both sides of a horizontal ridge. (IRC R324.6.2) Revise Roof #2/Roof #3 layout to provide the required clear setbacks.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
DENIED
Revise per building comments



PLUMBING REVIEW COMMENTS:
N/A