Permit Number: TC-RES-1222-01256
Parcel: 114468700

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1222-01256
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2023 Light Residential Building Review (OIP) APPROVED
01/06/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
12/22/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1222-01256

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2.
NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE GROUNDING/BONDING DETAILS AND DIAGRAM.
NEED THE TILE HOOK INSTALLATION INSTRUCTIONS INCLUDING THE SPACING.


BUILDING REVIEW COMMENTS:
DENIED
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2.
NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE GROUNDING/BONDING DETAILS AND DIAGRAM.
NEED A DOCUMENT SHOWING THE MODULE COMPATIBILITY FROM THE RACKING MANUFACTURER.
NEED THE TILE HOOK INSTALLATION INSTRUCTIONS INCLUDING THE SPACING.


MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
DENIED
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2.
NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE GROUNDING/BONDING DETAILS AND DIAGRAM.
NEED A DOCUMENT SHOWING THE MODULE COMPATIBILITY FROM THE RACKING MANUFACTURER.
NEED THE TILE HOOK INSTALLATION INSTRUCTIONS INCLUDING THE SPACING.
THE NEUTRAL AND GROUND ARE NOT SHOWN BONDED IN THE ELECTRICAL DIAGRAM OF THE MAIN DISCONNECT PANEL.
SPECIFY THE BACKFED BREAKER IS AT THE OPPOSITE END OF THE BUSBAR FROM THE MAIN DISCONNECT.


PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/08/2022 PDSD Application Completeness REVIEW COMPLETED