Permit Number: TC-RES-1222-01253
Parcel: 107130150

Address:
202 E GLENN ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1222-01253
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2023 Light Residential Building Review (OIP) APPROVED
01/06/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
12/16/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1222-01253

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2. ENGINEER CALCULATIONS ARE TO INCLUDE THEIR SEAL.
THE DESIGN WIND LOAD IS TO BE 115MPH.
NEED THE RACKING/BALLAST INSTALLATION INSTRUCTIONS INCLUDING THE GROUNDING/BONDING DETAILS AND DIAGRAM. INCLUDE BALLAST DETAILS FOR SUPPORT OF THE CONDUIT.


BUILDING REVIEW COMMENTS:
DENIED
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2. ENGINEER CALCULATIONS ARE TO INCLUDE THEIR SEAL.
THE DESIGN WIND LOAD IS TO BE 115MPH.
NEED THE RACKING/BALLAST INSTALLATION INSTRUCTIONS INCLUDING THE GROUNDING/BONDING DETAILS AND DIAGRAM. INCLUDE BALLAST DETAILS FOR SUPPORT OF THE CONDUIT.
NEED A DOCUMENT SHOWING THE MODULE COMPATIBILITY FROM THE RACKING/BALLAST MANUFACTURER.
DETAIL THE REQUIRED AC UNIT WORKSPACE IS NOT AFFECTED BY THE ARRAY.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
DENIED
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2. ENGINEER CALCULATIONS ARE TO INCLUDE THEIR SEAL.
THE DESIGN WIND LOAD IS TO BE 115MPH.
NEED THE RACKING/BALLAST INSTALLATION INSTRUCTIONS INCLUDING THE GROUNDING/BONDING DETAILS AND DIAGRAM. INCLUDE BALLAST DETAILS FOR SUPPORT OF THE CONDUIT.
NEED A DOCUMENT SHOWING THE MODULE COMPATIBILITY FROM THE RACKING/BALLAST MANUFACTURER.
THE NEUTRAL AND GROUND ARE NOT SHOWN BONDED IN THE ELECTRICAL DIAGRAM OF THE MAIN DISCONNECT PANEL.
THE MINIMUM TRENCH DEPTH IS 18".
SHOW THE EARTH GROUND AT THE HOUSE.
THE PV DISCONNECT IS NOT LESS THAN 10 FT TO THE SERVICE EQUIPMENT.
DETAIL THE REQUIRED AC UNIT WORKSPACE IS NOT AFFECTED BY THE ARRAY.
VERIFY EQUIPMENT IS READILY ACCESSIBLE AS REQUIRED BY UTILITY COMPANY AND EMERGENCY PERSONNEL.
DETAIL THAT THE BACKFED BREAKER IS AT THE OPPOSITE END OF THE BUSBAR FROM THE MAIN BREAKER.
DERATION FOR THE NUMBER OF CONDUCTORS IN THE RACEWAYS IS NOT INCLUDED IN THE CALCULATIONS.
CONDUIT HEIGHT ABOVE THE ROOF SHOWN IN THE TABLE ON PAGE E1.3 IS ONLY 1/2" - NEEDS ADDITIONAL DERATING IF CORRECT.


PLUMBING REVIEW COMMENTS:
N/A



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov