Permit Number: TC-RES-1222-01225
Parcel: 133372330

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1222-01225
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2023 Light Residential Building Review (OIP) APPROVED
01/05/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/15/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1222-01225

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2.
NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE APPROVAL OF USING THE E-CURB MOUNTS TO SUPPORT THE RACKING. ONLY TWO OF THE FOUR MOUNTING BLTS WILL LIKELY ATTACH TO THE FRAMING.
NEED THE TILE HOOK INSTRUCTIONS SHOWING THE SPACING REQUIREMENTS


BUILDING REVIEW COMMENTS:
DENIED
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2.
NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE APPROVAL OF USING THE E-CURB MOUNTS TO SUPPORT THE RACKING. ONLY TWO OF THE FOUR MOUNTING BLTS WILL LIKELY ATTACH TO THE FRAMING.
NEED THE TILE HOOK INSTRUCTIONS SHOWING THE SPACING REQUIREMENTS.
VERIFY EQUIPMENT IS READILY ACCESSIBLE AS REQUIRED BY UTILITY COMPANY AND EMERGENCY PERSONNEL.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
DENIED
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2.
NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE APPROVAL OF USING THE E-CURB MOUNTS TO SUPPORT THE RACKING. ONLY TWO OF THE FOUR MOUNTING BLTS WILL LIKELY ATTACH TO THE FRAMING.
NEED THE TILE HOOK INSTRUCTIONS SHOWING THE SPACING REQUIREMENTS.
THE NEUTRAL AND GROUND ARE NOT SHOWN BONDED IN THE ELECTRICAL DIAGRAM OF THE MAIN DISCONNECT PANEL.
VERIFY EQUIPMENT IS READILY ACCESSIBLE AS REQUIRED BY UTILITY COMPANY AND EMERGENCY PERSONNEL.


PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/07/2022 PDSD Application Completeness Express REVIEW COMPLETED