| 11/10/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact PDSD-Permits@tucsonaz.gov Please resubmit addressing the following comments: 1) A Surge Protection Device (SPD) must be identified on the plans. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL-listed and code-compliant with E606.5, NEC 230.67, and/or by providing the model number of the Surge Protection Device (SPD) to be installed. The SPD must have a nominal discharge current rating of not less than 10 kA, be UL 1449 listed, and be Type 1 or Type 2, in accordance with NEC 230.67. 2) Please read and initial the last two statements on Owner Builder Affidavit |
||
| 11/10/2026 | PDSD Application Completeness Express | REVIEW COMPLETED | For questions: PDSD-Permits@tucsonaz.gov. Your Owner Builder Affidavit (OBA) requires resubmit. Please initial both boxes with your first and last initial where it says "PLEASE READ AND INITIAL THE FOLLOWING:" instead of marking with a checkmark. Step-by-Step instructions on how to resubmit:  https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf |