Permit Number: TC-RES-1126-06206
Parcel: 108164030

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1126-06206
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/10/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Provide a comment response letter and address the following comments:
1) Provide load calculations including the EV charger (Standard or Optional are accepted). As of Jan. 1, the City of Tucson has adopted the 2024 I-codes and 2023 NEC. Verify that all calculations adhere to the variables present in the new code. EVSE to be calculated at a minimum of 7.2 kW or nameplate rating, whichever is greater. Conductors and OCPDs are to be sized as continuous loads (80% rule) 220.57
2) Provide Manufacturer Specifications of the EV charger to be used. Include any certifications to ensure that the EVSE is UL listed E3403.3
3) EV charger must be GFCI-capable, alternatively provide a means of GFCI protection (including GFCI Overcurrent Protection Devices (OCPD)) 625.54
4) Provide the nameplate rating of the EVSE (within Manufacturer specifications) to determine sizing of the breaker. Overcurrent protection (breaker) and conductors for feeders and branch circuits supplying EVSE and WPTE, shall be sized for continuous duty and shall have a current rating of not less than 125 percent of the maximum load of the equipment 625.41
11/09/2026 PDSD Application Completeness Express REVIEW COMPLETED Completeness check done