Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1126-06159
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/05/2026 | Residential Engineering Express | APPROVED | Approved - work within a floodplain permit is associated with TC-RES-1126-06159. FPU permit will be issued once fees are processed | ||
| 11/05/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/05/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact PDSD-Permits @tucsonaz.gov Please resubmit addressing the following comments: 1) There's a Code Violation for unit 1 (CE-VIO1126-04527). Please make sure to address ALL Code comments regarding electrical, plumbing, and gas systems. 2) A Surge Protection Device (SPD) must be identified on the plan. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL-listed and code-compliant with E606.5, NEC 230.67, and/or by providing the model number of the Surge Protection Device (SPD) to be installed. The SPD must have a nominal discharge current rating of not less than 10 kA, be UL 1449 listed, and be Type 1 or Type 2, in accordance with NEC 230.67. |
||
| 11/05/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |