Permit Number: TC-RES-1126-06151
Parcel: 121060620

Address:
5632 E MABEL ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1126-06151
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/05/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:
1) Provide an electrical load calculation (Standard or Optional is accepted). As of Jan. 1, the City of Tucson has adopted the 2024 I-codes and 2023 NEC. Verify that all calculations adhere to the variables present in the new code.
2) Show the rating of the subpanel and how the subpanel will branch from the main service panel (OCPD rating, conductor sizing, neutrals, and ground).
3) Show the location of the main service panel and a one line showing the route of the raceway between panels. Indicate if any raceway will be underground if applicable
4) Working clearance for the sub-panel must adhere to IRC Ch. 34
11/04/2026 PDSD Application Completeness Express REVIEW COMPLETED