Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-1125-05512
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2025 | Residential Zoning | APPROVED | |||
| 12/05/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/05/2025 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | Please resubmit addressing the following comments: 1) Conductor between the Service Panel to the Gateway and Gateway to Backup Loads Panel is undersized. NEC 230.42(A)(1) Please indicate which load panel the listed load calculations are being used to determine adequate conductor sizing. 2) 225 A Sub-feed Lug is oversized based on NEC 408.36, Please revise the size of this piece of equipment and demonstrate adherence to NEC 310.15(B)(16) showing whether the copper or aluminum to be used. For any questions, please email: PDSD-Residential@tucsonaz.gov |
||
| 11/13/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |