Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-RES-1125-05326
Parcel: 136080810

Address:
9641 E 32ND ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1125-05326
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/06/2025 Addressing Validation REQUIRES RESUBMIT Please ensure that the address on the site plan and other documents match the address on the permit. The address on the second page of the construction plan is 8641 instead of 9641. The wrong address is also included on the energy analysis documents. Please resubmit after all reviews have been completed.

Step-by-step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf

For questions: PDSD-Residential@tucsonaz.gov
11/10/2025 Residential Building REQUIRES RESUBMIT TC-RES-1125-05326
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments and building ordinances for all dwellings. The 2024 IRC will be in effect Jan 1, 2026.

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

GENERAL COMMENTS :

1. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.
2. Plans submitted for a newly constructed one- or two-family dwelling after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 .
a. Show a minimum 300 SF clear solar-ready zone on a roof or framing plan, T103.3.
b. Label a double breaker space for future Photo Voltaic on the panel schedule opposite end from the main/supply side, T103.9. Relocate the future PV breaker space at the last panel space.
3. Plans submitted for a newly constructed one- or two-family dwelling after June 1, 2010, require gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. The ordinance revision now requires a gray drain line discharge from one fixture for a one-story dwelling. Additional gray fixture drains are optional. Show a second clothes washer standpipe plumbed to an exterior wall above grade. Use the appropriate detail at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Water-Energy-Conservation Gray Water Illustrations
4. Show compliance with the Electric Vehicle Supply Equipment Ordinance adopted by the City of Tucson Ordinance #11844 on 6/22/2021. Show the location of the NEMA 14-50R receptacle for charging an electric vehicle.

PLANS:

1. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. Include the threshold condition at the vehicle doorway or an exterior hinged door when the garage is used for the accessible route.

SECTIONS - DETAILS:

1. Show one-hour fire-resistive framed construction separating dwellings in compliance with IBC Table 721.1(2).
2. Show the minimum dimension between floor and bottom of footing as 18”, R317.1 item 5 and R403.1.4. The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1. Update detail #1 and 2, sheet D-1.0.
3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Clarify the ceiling/roof insulation detail showing the air-impermeable rigid insulation material adhered to either side of the roof sheathing along with the batt insulation. Update details #1, 2 and 4, sheet D-2.0.

PLUMBING PLANS:

1. Show each gas pipe segment sized in conformance with Table G2413.4(1). Update the 170’ developed length entry at the gas line information schedule.
2. Consider relocating the gas meter with Southwest Gas coordination. The enclosure of new structure on three sides and roof provides restricted regulator ventilation, M1202.1.

MECHANICAL PLANS:

1. Provide demand calculations in accordance with Manual J standards, M1401.3, M1601.1.

ELECTRICAL PLANS:

1. Include the Electric Vehicle load entry (typically 7680 watts) in the electrical load calculations (continuous demand) like the HVAC entry, N1104.2.2.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
11/12/2025 Residential Engineering REQUIRES RESUBMIT Permit: TC-RES-1125-05326
Location: 9641 E 32ND ST
Review Date: 11/12/2025
Site Engineering Comments:
1. According to the Braewood Terrace final Plat, there exists a 5’ utility easement that runs along the East portion of the property. It is required that this easement be shown and called out on the plan.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
11/14/2025 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Claire Leighou, Planner

PROJECT: TC-RES-1125-05326

9641 E 32ND ST

Replace Fire Damaged SFR (1st Review)

TRANSMITTAL DATE: 11/14/25

Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 -.9.
Comment: Per the Addressing Validation comment, please ensure the correct address is listed on all pages.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code

If you have any questions about this transmittal, please contact Claire Leighou at claire.leighou@tucsonaz.gov. Thank you!
11/06/2025 PDSD Application Completeness Express REVIEW COMPLETED