Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Permit Number - TC-RES-1124-06940
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/24/2025 | Other Inspection Reports (Deferred Submittal) Express | APPROVED | Mechanical Load Calcs - Manual J | ||
| 04/24/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/24/2025 | Truss Design (Deferred Submittal) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-RES-1124-06940 ADDRESS/PARCEL: (1829 E 7TH ST Unit:UNIT 2 TUCSON, AZ 85719) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. Comments: Truss Design 1. The dimensions of the structure in the truss report do not match the dimensions on the floor plan (Sheet A2). The floor plan shows a length of 32’ - 1 ½”. This truss design report shows 31 - 4 ½”. Please fix the dimension and corresponding truss lengths. 2. Please resubmit |
||
| 04/22/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |