Permit Number: TC-RES-1124-06940
Parcel: 124031810

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - TC-RES-1124-06940
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2025 Other Inspection Reports (Deferred Submittal) Express APPROVED Mechanical Load Calcs - Manual J
04/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/24/2025 Truss Design (Deferred Submittal) Express REQUIRES RESUBMIT ACTIVITY NO. TC-RES-1124-06940
ADDRESS/PARCEL: (1829 E 7TH ST Unit:UNIT 2 TUCSON, AZ 85719)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
Comments:
Truss Design
1. The dimensions of the structure in the truss report do not match the dimensions on the floor plan (Sheet A2). The floor plan shows a length of 32’ - 1 ½”. This truss design report shows 31 - 4 ½”. Please fix the dimension and corresponding truss lengths.
2. Please resubmit
04/22/2025 PDSD Application Completeness Express REVIEW COMPLETED