Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1124-06924
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/27/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/27/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1124-06924 (3439 E 4TH ST TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. The 1” pipe from the meter to the first junction point( first 101') is undersized for the given load (190,000) and length (130’) on Line 2. See Table G2413.4(1). 2. Size the pipe based on the length from the meter to the farthest attached appliance and max total Branch demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1. 3. Clarify if the pool heater and gas appliances are all new and converted from electric. Or is this a re-pipe to existing gas appliances? Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||