Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.3
Permit Number - TC-RES-1124-06894
Review Name: RESIDENTIAL SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/02/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/02/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1124-06894 (3020 E 6TH ST Unit:UNIT 28 TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). Plumbing Review: 1. Show new drain connection in compliance with Table 3005.4.1. A maximum of 3 Drainage Fixture Units are allowed on a 1 ½” drain line. (see Table 3004.1 for Drainage Fixture Units per fixture). Mechanical Review: 2. Show dryer vent size and location for venting to exterior, M1501. Electrical Review: 3. Provide new washer and dryer circuiting information. Show circuit numbers, breaker size and conductor sizes. 4. Provide GFCI protection for all 15 and 20 amp receptacles in the laundry area, E3902.9. 5. Show a minimum of one 20 AMP branch circuit in the laundry area; this circuit may not serve other locations, E3703.3 and 3901.8. Contact PDSD-Residential@tucsonaz.gov |
||
| 12/02/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |