Review Details: RESIDENTIAL SOLAR REVISION v.1
Permit Number - TC-RES-1124-06862
Review Name: RESIDENTIAL SOLAR REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/22/2025 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-RES-1124-06862 ADDRESS/PARCEL: (4543 S 14TH AV TUCSON, AZ 85714) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. COMMENTS: 1. For the 60-amp backfeed breaker, please ensure that the conductors are sized appropriately. Copper conductors going from the SolarEdge inverter to the 60 amp backfeed breaker should be at least 6 AWG (IRC Table 3705.1). 2. Is the PV Breaker on the MSP going to be 30A like it was on the subpanel? 30A breaker is still listed in table on Sheet PV-6. 3. Please remove the note “existing wire run through conduit” and the wording “Subpanel Breaker” next to the 60A breaker on the MSP. Sheet PV-4 and PV-4A 4. Please resubmit Contact Sean Severson with any questions: sean.severson@tucsonaz.gov |
||