Permit Number: TC-RES-1124-06838
Parcel: 121101050

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-1124-06838
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/03/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1124-06838 (4814 E HAMPTON ST Unit:UNIT 1 TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Note the size of the feeder conductor to the 100A panel on the plans, E3602.1 & E3603.1.
2. Provide an electrical riser diagram, E3604, include breaker/fuse sizes for overcurrent protection of feeder. Notate the grounding and bonding method, E3607. Metallic gas lines must be bonded and not be used as the primary grounding method, E3608.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/03/2024 PDSD Application Completeness Express REVIEW COMPLETED