Permit Number: TC-RES-1124-06471
Parcel: 13637315A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1124-06471
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2024 Site Engineering NOT REQUIRED
12/06/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/25/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1124-06471 (4013 S SHADY PALM DR TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

>> Missing required structural calculations:
1. For wind uplift use 115 mph in 3sec gust, Table R301.2(1). https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf
2. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, or provide an engineer’s calculation, and sealed design, R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems

Fire separation:
3. Rooftop-mounted PV panels and modules within 3 of the property line require fire ratings or separation per R324.4.2. Rooftop-mounted photovoltaic panels and modules must have a fire classification of Class A, B or C in accordance with UL 1703 or UL2703, R902.4.
4. Provide PV fire classification rating.

Mechanical:
5. Add the following note to the PV Module layout sheets: Maintain working space around mechanical equipment (HVAC) per M1305.1 & M1401.2.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov