Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-1123-09842
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/21/2023 | Site Engineering | NOT REQUIRED | |||
| 12/21/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/13/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. 1) WIre #5 size on PV-03 not in wire schedule. Please add to plans. Also verify address and unit number being serviced, revise plans and engineering documents to reflect the correct unit. 2) NEC 240.21(B) show compliance with feeder tap requirements per section. Provide the length of the tap conductors and feeder conductor. Building_official@tucsonaz.gov |
||