Permit Number: TC-RES-1123-09828
Parcel: 129052500

Address:
3025 E 18TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1123-09828
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2024 Site Engineering NOT REQUIRED
01/02/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/14/2023 Residential Building REQUIRES RESUBMIT TC-RES-1123-09828
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

Provide the permit number for the existing structure or provide plans showing that the existing structure is code compliant for a dwelling unit.

Provide a complete construction plan set. Sample plans are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

1. Provide a site plan showing dimensions of buildings and utilities, R106.1.1. Show the location of all utility lines from property line to building(s) along with required alterations. Identify utility lines requiring alterations, R106.1.1.
2. Show the location and square footage of the workshop and shed.

FLOOR PLAN:

1. The sleeping room exterior door is compliant for egress, R310.

STRUCTURAL PLANS:

2. Provide complete structural (roof framing) plans showing compliance with the IRC or provide an Arizona structural engineer plan set showing performance compliance, R301.1. Show all proposed repairs and alterations with 2018 IRC compliance, R301.1.
3. The proposed Patio Cover may be sited within the 3’ fire separation distance from a property line. Show compliance with R302.1 (City of Tucson Amended) by providing a wall with one-hour rated materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3, R106.1 or remove any structure closer than 3 feet to the neighboring property line.

SECTIONS - DETAILS:

1. Provide a structure section showing existing and proposed features including a foundation, sills, anchoring, framing, sheathing and insulation, R106.1.
2. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show with dimensions the exterior wood siding, insulation, interior sheathing, and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.

PLUMBING PLANS:

1. Provide complete plumbing plans showing 2018 IRC compliance, R301.1.
2. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe for supporting the existing and proposed dwelling units.
3. Show an individual accessible water supply shut off and water heater for the proposed dwelling building, P2903.9.1.

MECHANICAL PLANS:

1. Show the heating/cooling capacity, R303.9.

ELECTRICAL PLANS:

1. Provide a Riser Diagram showing a sub panel and feeder size for proposed sleeping quarters, NEC 225.30, E3403, Table E3704.2(1).
2. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, E3404.12.
3. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2.
4. Show a smoke alarm, R314.3.
5. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
6. Show a switch controlled light at the outdoor entrance, E3903.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details minimum (R-13 walls and R-30 small additions or otherwise R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better.

OUTDOOR LIGHTING CODE

Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
12/14/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-RES-1123-09828
3025 E 18TH ST Zoning R-1

TRANSMITTAL DATE:‎December 14, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Provide a Residential Plot Plan that meets the requirements found at: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/permits/residential-permits/residential_plot_plan_requirements.pdf
This shall in include:
a. Lot coverage calculation that meets the requirements of UDC Article 6.4.3 & the example shown on the residential plot requirements. (Lot coverage must include vehicular use area whether improved or unimproved) . Lot coverage does not include porches, UDC Article 6.4.3.C.1.a but does include vehicle use area measured within the outside edges of any area allocated to vehicle use, whether improved or unimproved.

b. Zoning of adjacent parcels
c. All Utility lines
d. Property line distances
Comment: Provide a floor plan for the existing residence on the plan so that Zoning can verify if the requirements of UDC Article 4.9.7.B.7 are applicable to this project. UseSpecific Standards 4.9.7.B.7 which states “ For any new single-family dwelling in the R-1 zone with five bedrooms , three parking spaces are required.For every bedroom over five, one additional space is required for each bedroom . For all single-family dwellings in the R-1 zone with five or more bedrooms , and for all lots containing two or more single-family dwellings, with the second dwelling having more than one bedroom , all parking spaces must be located on-site , either in a side or rear perimeter yard . Parking spaces may not be located in a vehicular use area in any front street perimeter yard . A parking area is not required to be developed to a commercial standard. A dustproof parking surface is required to at least a minimum of two inches of compacted pea gravel. An existing covered residential parking area may be used.