Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1123-09818
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/30/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/30/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1123-09527 (2526 E ALTURAS ST TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). Gas review: 1. Note and specify all piping materials on the plans, G2412.9. 2. Provide the total length measured from the gas meter to the Heater, G2415.17. 3. 3. Provide the total demand of the heater on the plans, Table G2413.4(7). a. Size the pipe based on the length from the meter to Pool Heater and max total demand of the heater, Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the Pool Heater, G2413.4.1. 4. Provide a Yellow tracer wire for non-metallic pipe, G2415.17.3. Electrical Review: 5. Provide conductor type and conduit type and size, per E3803. Use the correct conductor type rated for the given use, E3801.2. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 11/30/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |