Permit Number: TC-RES-1123-09758
Parcel: 132091360

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1123-09758
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2023 Site Engineering NOT REQUIRED
12/20/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/15/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT TC-RES-1123-09758 Resubmit comment

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Sheet PV-4, OCPD for copper conductor may not exceed 30A for #10 rating required by NEC 240.4(D) (small conductors), For larger than #10AWG, see NEC Table 310.15(B)(16)